QA4Exam focus on the latest syllabus and exam objectives, our practice Q&A are designed to help you identify key topics and solidify your understanding. By focusing on the core curriculum, These Questions & Answers helps you cover all the essential topics, ensuring you're well-prepared for every section of the exam. Each question comes with a detailed explanation, offering valuable insights and helping you to learn from your mistakes. Whether you're looking to assess your progress or dive deeper into complex topics, our updated Q&A will provide the support you need to confidently approach the NFPA CFPE exam and achieve success.
What is the maximum floor area on any one floor permitted to be protected by a single sprinkler system riser for an ordinary hazard occupancy?
According to NFPA 13, Standard for the Installation of Sprinkler Systems, the maximum floor area permitted to be protected by a single sprinkler system riser for an ordinary hazard occupancy is 40,000 square feet (3,716 square meters). This limit ensures adequate water delivery pressure and flow to all sprinklers in the covered area.
Exhibit.
What is the occupant load of the cafetorium on plan A5 if me room is set up for a less concentrated use without fixed seating'?
The occupant load for a space without fixed seating is typically calculated based on the occupancy type and its use. According to NFPA 101, Life Safety Code, for a room set up for less concentrated use (such as a cafetorium without fixed seating), the occupant load factor is usually 15 square feet per person. If the total area of the cafetorium is approximately 5,910 square feet (394 occupants), then dividing the total area by 15 gives an occupant load of 394 persons.
A 4 in. (101.6 mm) riser requires what minimum diameter pipe for the combination mam drain and alarm test connection?
For a 4-inch (101.6 mm) riser, the minimum diameter pipe for the combination main drain and alarm test connection should be 1 inch (25.4 mm). This size is specified to ensure adequate water flow during a test or when draining the system, in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.
Exhibit.
Given the layout shown in the figure, with handrails 38 inches (965 mm) m height what is the available egress width at point B?
Based on the figure, point B appears to represent a location where the egress path is narrowed due to handrails or other obstructions. The available egress width at point B is 41 inches (1,041 mm), considering the encroachment of the handrails into the stairwell.
For the purposes of fire sprinkler protection, occupancies where combustibility is low. quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 ft (2.4 m). are called
Occupancies where the combustibility is low, the quantity of combustibles is moderate, and stockpiles of combustibles do not exceed 8 feet (2.4 meters) are classified as 'Ordinary hazard (Group 1).' This classification, as defined in NFPA 13, Standard for the Installation of Sprinkler Systems, is used to determine the design density and spacing of sprinklers required to provide adequate fire protection.